450/750V & 600V/1000V Single-Core
Mica Tape Fire Barrier, LSZH Insulated, Non-Sheathed
Fire Resistant Cable
 |
Application : |
This cable is used in fire extinguishing systems, sprinkler systems, control panels, and exit lights in high-rise buildings, hotels, hospitals, sub-ways, and public facilities. |
Voltage rating : |
450/750V & 600/1000V |
Construction : |
Plan annealed copper, Mica tape fire barrier, LSZH Compound insulated cable |
Insulation colour : |
Orange or As per order |
Specification : |
Refer BS7211, BS6387, SS299-1, IEC60331, IEC60332-1, IEC60332-3, IEC60754, IEC61034 |
| Conductor |
450/750V |
600/1000V |
| Nominal Thickness of nsulation |
Approx. O/D of Cable |
Approx. Weight of Cable |
Nominal Thickness of Insulation |
Approx. O/D of Cable |
Approx. Weight of Cable |
Size |
No./Dia. of Strand |
mm2 |
No./mm |
mm |
mm |
kg/km |
mm |
mm |
kg/km |
1.5 |
7/0.53 |
0.7 |
3.5 |
24 |
0.8 |
3.8 |
30 |
2.5 |
7/0.67 |
0.8 |
4.1 |
36 |
0.8 |
4.2 |
40 |
4 |
7/0.85 |
0.8 |
4.6 |
52 |
1.0 |
5.3 |
70 |
6 |
7/1.04 |
0.8 |
5.2 |
72 |
1.0 |
6.0 |
96 |
10 |
7/1.35 |
1.0 |
6.5 |
119 |
1.0 |
6.6 |
130 |
16 |
7/1.70 |
1.0 |
7.6 |
178 |
1.0 |
7.7 |
195 |
25 |
7/2.14 |
1.2 |
9.0 |
275 |
1.2 |
9.1 |
290 |
35 |
7/2.52 |
1.2 |
10.2 |
370 |
1.2 |
10.3 |
385 |
50 |
19/1.78 |
1.4 |
11.8 |
504 |
1.4 |
11.9 |
524 |
70 |
19/2.14 |
1.4 |
13.4 |
706 |
1.4 |
13.5 |
730 |
95 |
19/2.52 |
1.6 |
15.8 |
974 |
1.6 |
15.9 |
990 |
120 |
37/2.03 |
1.6 |
17.1 |
1212 |
1.6 |
17.2 |
1250 |
150 |
37/2.25 |
1.8 |
18.8 |
1487 |
1.8 |
18.9 |
1520 |
185 |
37/2.52 |
2.0 |
21.0 |
1860 |
2.0 |
21.2 |
1900 |
240 |
61/2.25 |
2.2 |
25.7 |
2512 |
2.2 |
25.8 |
2550 |
300 |
61/2.52 |
2.4 |
28.6 |
3138 |
2.4 |
28.8 |
3150 |
400 |
61/2.85 |
2.6 |
32.0 |
3980 |
2.6 |
32.2 |
4000 |
500 |
61/3.20 |
2.8 |
35.5 |
4990 |
2.8 |
35.7 |
5000 |
630 |
127/2.52 |
2.8 |
39.5 |
6302 |
2.8 |
39.7 |
6360 |
|