600/1000V 2-Core ~ 4-Core
XLPE Insulated, Unarmoured & Armoured,
PVC Sheathed Cable
 |
Application : |
This cable is primarily used for main power supply. It is also used for industrial installations, such as in cable ducts, in cable trunking, on cable trays, on cable ladders and in switchgears. |
Voltage rating : |
600/1000V |
Construction : |
Plain annealed copper, XLPE insulated, Unarmoured or Galvanized Steel wires armoured, PVC sheathed cable |
Insulation colour : |
2-Core: (Red & Black)
3-Core: (Red, Yellow & Blue)
4-Core: (Red, Yellow, Blue & Black) |
Sheath colour : |
Black |
Specification : |
IEC60502-1 |
| 2-CORE |
| Cond. Nominal Area |
Thickness of Insulation |
Unarmoured Cable |
Wires Armoured Cable |
| Thickness of Sheath |
Approx. Overall Dia. |
Approx. Cable Weight |
Thickness of Bedding |
Nominal Armour Wire Dia. |
Thickness of Sheath |
Approx. Overall Diameter |
Approx. Cable Weight |
| Extruded |
Lapped |
Extruded |
Lapped |
Extruded |
Lapped |
mm2 |
mm |
mm |
mm |
kg/km |
mm |
mm |
mm |
mm |
mm |
mm |
kg/km |
kg/km |
1.5 (cs) |
0.7 |
1.8 |
10.1 |
130 |
1.0 |
- |
0.90 |
1.8 |
14.0 |
- |
350 |
- |
2.5 (cs) |
0.7 |
1.8 |
10.6 |
160 |
1.0 |
- |
0.90 |
1.8 |
14.8 |
- |
410 |
- |
4 (cs) |
0.7 |
1.8 |
12.0 |
205 |
1.0 |
- |
0.90 |
1.8 |
16.6 |
- |
490 |
- |
6 (cs) |
0.7 |
1.8 |
13.1 |
260 |
1.0 |
- |
0.90 |
1.8 |
17.5 |
- |
580 |
- |
10 (cs) |
0.7 |
1.8 |
15.0 |
375 |
1.0 |
- |
1.25 |
1.8 |
19.5 |
- |
800 |
- |
16 (cs) |
0.7 |
1.8 |
17.2 |
530 |
1.0 |
- |
1.25 |
1.8 |
22.5 |
- |
1048 |
- |
25 (s) |
0.9 |
1.8 |
17.0 |
655 |
1.0 |
0.8 |
1.60 |
1.8 |
21.5 |
21.0 |
1270 |
1255 |
35 (s) |
0.9 |
1.8 |
18.5 |
865 |
1.0 |
0.8 |
1.60 |
1.8 |
24.5 |
23.1 |
1530 |
1510 |
50 (s) |
1.0 |
1.8 |
21.0 |
1135 |
1.0 |
0.8 |
1.60 |
1.8 |
26.0 |
25.6 |
1870 |
1830 |
70 (s) |
1.1 |
1.8 |
23.5 |
1570 |
1.0 |
0.8 |
1.60 |
2.0 |
29.5 |
29.1 |
2420 |
2390 |
95 (s) |
1.1 |
1.9 |
26.5 |
2120 |
1.2 |
0.8 |
2.00 |
2.1 |
33.5 |
32.2 |
3350 |
3300 |
120 (s) |
1.2 |
2.0 |
29.5 |
2640 |
1.2 |
0.8 |
2.00 |
2.2 |
36.5 |
35.2 |
3990 |
3800 |
150 (s) |
1.4 |
2.2 |
33.0 |
3250 |
1.2 |
0.8 |
2.00 |
2.3 |
39.5 |
38.2 |
4730 |
4710 |
185 (s) |
1.6 |
2.3 |
36.5 |
4050 |
1.4 |
0.8 |
2.50 |
2.5 |
44.5 |
43.3 |
6200 |
6130 |
240 (s) |
1.7 |
2.5 |
46.0 |
5300 |
1.4 |
0.8 |
2.50 |
2.7 |
53.0 |
52.3 |
7780 |
7720 |
300 (s) |
1.8 |
2.6 |
50.0 |
6590 |
1.6 |
0.8 |
2.50 |
2.8 |
58.0 |
56.4 |
9390 |
9280 |
400 (s) |
2.0 |
2.9 |
54.0 |
8365 |
1.6 |
0.8 |
2.50 |
3.1 |
62.0 |
61.0 |
11475 |
11370 |
| 3-CORE |
| Cond. Nominal Area |
Thickness of Insulation |
Unarmoured Cable |
Wires Armoured Cable |
| Thickness of Sheath |
Approx. Overall Dia. |
Approx. Cable Weight |
Thickness of Bedding |
Nominal Armour Wire Dia. |
Thickness of Sheath |
Approx. Overall Diameter |
Approx. Cable Weight |
| Extruded |
Lapped |
Extruded |
Lapped |
Extruded |
Lapped |
mm2 |
mm |
mm |
mm |
kg/km |
mm |
mm |
mm |
mm |
mm |
mm |
kg/km |
kg/km |
1.5 (cs) |
0.7 |
1.8 |
10.5 |
145 |
1.0 |
- |
0.90 |
1.8 |
14.5 |
- |
391 |
- |
2.5 (cs) |
0.7 |
1.8 |
11.3 |
190 |
1.0 |
- |
0.90 |
1.8 |
15.5 |
- |
435 |
- |
4 (cs) |
0.7 |
1.8 |
12.5 |
250 |
1.0 |
- |
0.90 |
1.8 |
17.0 |
- |
550 |
- |
6 (cs) |
0.7 |
1.8 |
13.9 |
320 |
1.0 |
- |
1.25 |
1.8 |
18.5 |
- |
660 |
- |
10 (cs) |
0.7 |
1.8 |
15.9 |
480 |
1.0 |
- |
1.25 |
1.8 |
20.4 |
- |
900 |
- |
16 (cs) |
0.7 |
1.8 |
18.1 |
690 |
1.0 |
- |
1.25 |
1.8 |
23.4 |
- |
1260 |
- |
25 (s) |
0.9 |
1.8 |
20.0 |
920 |
1.0 |
0.8 |
1.60 |
1.8 |
25.0 |
24.6 |
1630 |
1610 |
35 (s) |
0.9 |
1.8 |
22.0 |
1200 |
1.0 |
0.8 |
1.60 |
1.8 |
27.0 |
26.6 |
1995 |
1955 |
50 (s) |
1.0 |
1.8 |
24.5 |
1655 |
1.0 |
0.8 |
1.60 |
1.9 |
30.5 |
30.1 |
2520 |
2500 |
70 (s) |
1.1 |
1.9 |
28.0 |
2230 |
1.2 |
0.8 |
2.00 |
2.0 |
35.0 |
34.2 |
3585 |
3535 |
95 (s) |
1.1 |
2.0 |
32.0 |
3100 |
1.2 |
0.8 |
2.00 |
2.2 |
38.5 |
37.7 |
4590 |
4550 |
120 (s) |
1.2 |
2.1 |
35.5 |
3850 |
1.2 |
0.8 |
2.00 |
2.3 |
42.0 |
41.3 |
5530 |
5500 |
150 (s) |
1.4 |
2.3 |
40.0 |
4830 |
1.4 |
0.8 |
2.50 |
2.5 |
47.5 |
46.2 |
7000 |
6860 |
185 (s) |
1.6 |
2.4 |
44.0 |
6000 |
1.4 |
0.8 |
2.50 |
2.6 |
52.0 |
50.7 |
8460 |
8320 |
240 (s) |
1.7 |
2.6 |
53.5 |
7810 |
1.6 |
0.8 |
2.50 |
2.8 |
62.0 |
60.4 |
10550 |
10260 |
300 (s) |
1.8 |
2.7 |
60.0 |
9875 |
1.6 |
0.8 |
2.50 |
3.0 |
68.5 |
67.4 |
12530 |
12300 |
400 (s) |
2.0 |
3.0 |
65.5 |
12180 |
1.6 |
0.8 |
2.50 |
3.2 |
74.0 |
72.4 |
16520 |
15310 |
| 4-CORE |
| Cond. Nominal Area |
Thickness of Insulation |
Unarmoured Cable |
Wires Armoured Cable |
| Thickness of Sheath |
Approx. Overall Dia. |
Approx. Cable Weight |
Thickness of Bedding |
Nominal Armour Wire Dia. |
Thickness of Sheath |
Approx. Overall Diameter |
Approx. Cable Weight |
| Extruded |
Lapped |
Extruded |
Lapped |
Extruded |
Lapped |
mm2 |
mm |
mm |
mm |
kg/km |
mm |
mm |
mm |
mm |
mm |
mm |
kg/km |
kg/km |
1.5 (cs) |
0.7 |
1.8 |
11.3 |
170 |
1.0 |
- |
0.9 |
1.8 |
15.3 |
- |
433 |
- |
2.5 (cs) |
0.7 |
1.8 |
12.3 |
225 |
1.0 |
- |
0.9 |
1.8 |
17.0 |
- |
519 |
- |
4 (cs) |
0.7 |
1.8 |
13.8 |
305 |
1.0 |
- |
0.9 |
1.8 |
18.5 |
- |
635 |
- |
6 (cs) |
0.7 |
1.8 |
15.2 |
385 |
1.0 |
- |
1.25 |
1.8 |
19.8 |
- |
735 |
- |
10 (cs) |
0.7 |
1.8 |
17.5 |
580 |
1.0 |
- |
1.25 |
1.8 |
22.0 |
- |
1026 |
- |
16 (cs) |
0.7 |
1.8 |
20.0 |
835 |
1.0 |
- |
1.6 |
1.8 |
26.0 |
- |
1640 |
- |
25 (s) |
0.9 |
1.8 |
22.0 |
1210 |
1.0 |
0.8 |
1.6 |
1.8 |
27.5 |
27.0 |
2020 |
2010 |
35 (s) |
0.9 |
1.8 |
24.5 |
1610 |
1.0 |
0.8 |
1.6 |
1.9 |
30.5 |
26.6 |
2475 |
2457 |
50 (s) |
1.0 |
1.8 |
27.5 |
2120 |
1.0 |
0.8 |
1.6 |
2.0 |
33.5 |
32.6 |
3100 |
3080 |
70(s) |
1.1 |
2.0 |
31.5 |
3015 |
1.2 |
0.8 |
2.0 |
2.2 |
38.5 |
37.7 |
4480 |
4440 |
95 (s) |
1.1 |
2.1 |
36.5 |
4085 |
1.2 |
0.8 |
2.0 |
2.3 |
43.0 |
42.2 |
5735 |
5710 |
120 (s) |
1.2 |
2.3 |
41.0 |
5155 |
1.4 |
0.8 |
2.5 |
2.5 |
49.0 |
47.8 |
7460 |
7430 |
150 (s) |
1.4 |
2.4 |
46.5 |
6310 |
1.4 |
0.8 |
2.5 |
2.6 |
53.0 |
51.8 |
8810 |
8720 |
185 (s) |
1.6 |
2.6 |
51.5 |
7940 |
1.4 |
0.8 |
2.5 |
2.8 |
59.0 |
57.8 |
10780 |
10690 |
240 (s) |
1.7 |
2.8 |
58.5 |
10520 |
1.6 |
0.8 |
2.5 |
3.0 |
68.0 |
66.4 |
13600 |
13340 |
300 (s) |
1.8 |
3.0 |
64.0 |
13135 |
1.6 |
0.8 |
2.5 |
3.2 |
73.0 |
70.4 |
16200 |
15920 |
400 (s) |
2.0 |
3.3 |
73.0 |
16700 |
1.8 |
0.8 |
3.15 |
3.5 |
83.0 |
81.0 |
22230 |
22100 |
(cs) : Circular Stranded
(s) : Sector Shaped Stranded Conductors
|