| APPLICATION | This cable is used for urban networks. It can be installed aerially, in conduit, on open trays and in underground ducts. |
| VOLTAGE RATING |
26/35 kV |
| CONSTRUCTION | Conductor: Compact round stranded copper or
aluminium |
| SPECIFICATION | IEC60502-2 |
Detailed SpecificationNominal |
Reference |
Nominal |
Approx |
Approx weight of cable |
Approx |
Approx weight of cable |
||
Cu |
Al |
Cu |
Al |
|||||
Non Armoured |
Non Armoured |
Aluminium
Wire |
Aluminium
Wire |
|||||
mm2 |
mm |
mm |
mm |
kg/km |
kg/km |
mm |
kg/km |
kg/km |
50 |
8.4 |
10.5 |
38 |
1635 |
1356 |
50 |
5157 |
4887 |
70 |
10.0 |
10.5 |
40 |
1948 |
1516 |
51 |
5609 |
5117 |
95 |
11.7 |
10.5 |
41 |
2294 |
1676 |
53 |
6115 |
5495 |
120 |
13.1 |
10.5 |
43 |
2665 |
1849 |
55 |
6614 |
5808 |
150 |
14.6 |
10.5 |
44 |
2975 |
1999 |
56 |
7097 |
6121 |
185 |
16.2 |
10.5 |
46 |
3362 |
2191 |
58 |
7597 |
6426 |
240 |
18.4 |
10.5 |
49 |
4006 |
2479 |
61 |
8472 |
6945 |
300 |
20.6 |
10.5 |
51 |
4852 |
2868 |
63 |
9532 |
7549 |
400 |
23.8 |
10.5 |
55 |
5700 |
3218 |
67 |
10680 |
8198 |
500 |
26.6 |
10.5 |
60 |
6857 |
3771 |
72 |
12289 |
9201 |
630 |
30.0 |
10.5 |
62 |
8214 |
4323 |
74 |
13258 |
9366 |
800 |
34.0 |
10.5 |
66 |
9710 |
5030 |
79 |
15658 |
11008 |
1000 |
38.2 |
10.5 |
71 |
12059 |
5866 |
84 |
18523 |
12331 |
Continuous Current CapacityType |
XLPE Insulated Unarmoured |
|||||||
Arrange type |
Delta (connect each other) |
Flat (the space between adjacent cores is the overall diameter of the cable) |
||||||
Laying method Nominal cross- |
in air |
direct buried |
in air |
direct buried |
||||
Cu |
Al |
Cu |
Al |
Cu |
Al |
Cu |
Al |
|
50 |
215 |
170 |
260 |
200 |
250 |
190 |
225 |
175 |
70 |
270 |
210 |
320 |
250 |
305 |
240 |
275 |
215 |
95 |
330 |
255 |
390 |
300 |
375 |
290 |
335 |
260 |
120 |
380 |
295 |
445 |
345 |
435 |
335 |
380 |
295 |
150 |
430 |
330 |
500 |
395 |
490 |
380 |
425 |
330 |
185 |
490 |
380 |
570 |
440 |
565 |
435 |
485 |
375 |
240 |
575 |
450 |
665 |
515 |
665 |
520 |
565 |
438 |
300 |
660 |
515 |
750 |
585 |
760 |
590 |
635 |
495 |
400 |
765 |
600 |
865 |
680 |
890 |
695 |
730 |
570 |
500 |
875 |
695 |
980 |
775 |
1030 |
810 |
830 |
655 |
630 |
1010 |
810 |
1110 |
895 |
1200 |
950 |
950 |
755 |
800 |
1150 |
940 |
1250 |
1020 |
1380 |
1110 |
1080 |
865 |
1000 |
1260 |
1050 |
1360 |
1130 |
1540 |
1250 |
1190 |
960 |
Ambient Temperature ˚C |
40°C |
25°C |
40°C |
25°C |
||||
Operating Temperature ˚C |
90°C |
|||||||
Technical PropertiesMain Technical Properties
No |
Uo/U (kV) Rated Voltage Technical properties |
3.6/6 |
6/6 |
8.7/10 |
12/20 |
18/30 |
21/35 |
26/35 |
1 |
Conductor DC resistance (Ω/km) See next |
See next table |
||||||
2 |
Routine partial discharge test |
5 |
||||||
3 |
Routine AC. Voltage test |
12.6/5 |
21/5 |
30.5/5 |
42/5 |
63/5 |
73.5/5 |
91/5 |
4 |
Power frequency AC voltage test |
14.4 |
24 |
34.8 |
48 |
72 |
84 |
104 |
5 |
Hot Set Test |
130 |
||||||
6 |
Hot impact resistance test (kV) |
60 |
75 |
95 |
125 |
170 |
200 |
250 |
7 |
Other tests |
See Q / 320481LL019 - 2003 |
||||||
Conductor DC Resistance
Nominal cross-sectional area 20°C, the D.C. resistance |
25 |
35 |
50 |
70 |
95 |
120 |
150 |
185 |
Cu |
0.727 |
0.524 |
0.387 |
0.268 |
0.193 |
0.153 |
0.124 |
0.0991 |
Al |
1.20 |
0.868 |
0.641 |
0.443 |
0.320 |
0.253 |
0.206 |
0.164 |
Nominal cross-sectional area 20°C, the D.C. resistance |
240 |
300 |
400 |
500 |
630 |
800 |
1000 |
Cu |
0.0754 |
0.0601 |
0.0470 |
0.0366 |
0.0283 |
0.0221 |
0.0176 |
Al |
0.125 |
0.100 |
0.0778 |
0.0605 |
0.0469 |
0.0367 |
0.0291 |
Correction coefficient of current-carrying capacity under different ambient temperature
Operating temperature |
Ambient temperature (in air) (°C) |
||||||||
10 |
15 |
20 |
25 |
30 |
35 |
40 |
45 |
50 |
|
60 |
1.58 |
1.50 |
1.41 |
1.32 |
1.22 |
1.11 |
1.00 |
0.86 |
0.73 |
65 |
1.48 |
1.41 |
1.34 |
1.26 |
1.18 |
1.09 |
1.00 |
0.89 |
0.77 |
70 |
1.41 |
1.35 |
1.29 |
1.22 |
1.15 |
1.08 |
1.00 |
0.91 |
0.81 |
80 |
1.32 |
1.27 |
1.22 |
1.17 |
1.11 |
1.06 |
1.00 |
0.93 |
0.86 |
90 |
1.26 |
1.22 |
1.18 |
1.14 |
1.09 |
1.04 |
1.00 |
0.94 |
0.89 |
105 |
1.22 |
1.19 |
1.15 |
1.11 |
1.08 |
1.04 |
1.00 |
0.95 |
0.91 |
Operating temperature |
Ambient temperature (in soil) (°C) |
|||||
10 |
15 |
20 |
25 |
30 |
35 |
|
60 |
1.20 |
1.13 |
1.07 |
1.00 |
0.93 |
0.85 |
65 |
1.17 |
1.12 |
1.06 |
1.00 |
0.94 |
0.87 |
70 |
1.15 |
1.11 |
1.05 |
1.00 |
0.94 |
0.88 |
80 |
1.13 |
1.09 |
1.04 |
1.00 |
0.95 |
0.90 |
90 |
1.11 |
1.07 |
1.04 |
1.00 |
0.96 |
0.92 |
Correction coefficient of current-carrying capacity for different specific thermal resistivity of ground
Voltage |
Sectional area |
Specific thermal resistivity of ground ρ t (K.m/W) |
||||
(kV) |
(mm²) |
0.8 |
1.0 |
1.2 |
1.5 |
2.0 |
3.6/6 ~ 6/6 |
≤35 |
1.06 |
1.00 |
0.95 |
0.88 |
0.80 |
6/10 ~ 12/15 |
≤35 |
1.05 |
1.00 |
0.95 |
0.89 |
0.80 |
12/20 ~ 26/35 |
≤95 |
1.05 |
1.00 |
0.95 |
0.90 |
0.82 |
Correction coefficient of current rating capacity for multi - cables laid in parallel in air
Array |
Layer no. |
Layers x Pcs |
Gap between cable/cable Dia. |
Correction factor |
Note |
|
Plane parallel |
Level |
Vertical |
||||
One layer |
1 x 2 |
- |
< 5 |
0.89 |
d = Gap between cables |
|
1 x 3 |
- |
< 0.75 |
0.84 |
|||
Two layers |
2 x 1 |
< 0.5 |
1.9~1.5 |
0.99 |
||
1.4~1.0 |
0.97 |
|||||
< 0.5 |
0.90 |
|||||
2 x 2 |
< 0.5 |
2~1.5 |
0.99 |
|||
1.49~1.5 |
0.97 |
|||||
0.9~0.5 |
0.90 |
|||||
Three layers |
3 x 1 |
- |
4~3 |
0.99 |
||
2.9~2.0 |
0.97 |
|||||
1.9~1.0 |
0.94 |
|||||
< 0.5 |
0.85 |
|||||
3 x 2 |
< 0.5 |
4~3 |
0.99 |
|||
2.9~2.0 |
0.97 |
|||||
3 x 3 |
< 0.75 |
1.9~1.0 |
0.94 |
|||
< 0.5 |
0.85 |
|||||
Max. calculated permissible short - circuit for conductor
Nominal cross-section of |
Maximum permissible short-circuit for conductor (1 sec.) |
|
Maximum permissible short-circuit for conductor (1 sec.) |
Aluminium conductor |
|
10 |
1.51 |
0.988 |
16 |
2.39 |
1.56 |
25 |
3.69 |
2.42 |
35 |
5.15 |
3.37 |
50 |
7.31 |
4.79 |
70 |
10.2 |
6.68 |
95 |
13.8 |
9.03 |
120 |
17.4 |
11.4 |
150 |
21.7 |
14.2 |
185 |
26.7 |
17.5 |
240 |
34.6 |
22.6 |
300 |
43.1 |
28.2 |
400 |
57.4 |
37.6 |
500 |
71.7 |
47.0 |
630 |
88.8 |
58.0 |
Max. permissible short-circuit for current for metallic screen (copper tape screen)
Nominal |
Rated voltages of cable (kV) |
||||||
3.6/6 |
6/6 |
8.7/10 |
12/20 |
18/30 |
21/35 |
26/35 |
|
Short-Circuit Current A |
|||||||
25 |
1075 |
1083 |
1094 |
- |
- |
- |
- |
35 |
1074 |
1082 |
1092 |
1096 |
- |
- |
- |
50 |
1072 |
1080 |
1091 |
1095 |
1284 |
1286 |
1288 |
70 |
1070 |
1079 |
1090 |
1091 |
1281 |
1285 |
1286 |
95 |
1069 |
1077 |
1086 |
1272 |
1280 |
1284 |
1283 |
120 |
1068 |
1077 |
1286 |
1271 |
1279 |
1280 |
1282 |
150 |
1067 |
1076 |
1265 |
1270 |
1278 |
1279 |
1282 |
185 |
1064 |
1251 |
1264 |
1267 |
1275 |
1276 |
1279 |
240 |
1241 |
1250 |
1262 |
1266 |
1274 |
1275 |
1278 |
300 |
1239 |
1246 |
1261 |
1265 |
1270 |
1272 |
1277 |
400 |
1240 |
1245 |
1256 |
1260 |
1270 |
1272 |
1274 |
500 |
1243 |
1244 |
1253 |
1257 |
1266 |
1272 |
1273 |
630 |
1236 |
1238 |
1252 |
1253 |
1265 |
1270 |
1270 |
Capacitance of cable (reference value)
Nominal |
Rated voltages of cable (kV) |
||||||
3.6/6 |
6/6 |
8.7/10 |
12/20 |
18/30 |
21/35 |
26/35 |
|
Capacitance for each phase μ F/Km |
|||||||
25 |
0.2423 |
0.1922 |
0.1576 |
0.1378 |
0.1163 |
0.1064 |
0.0992 |
35 |
0.2684 |
0.1922 |
0.1725 |
0.1502 |
0.1251 |
0.1140 |
0.1061 |
50 |
0.3022 |
0.2367 |
0.1917 |
0.1661 |
0.1363 |
0.1239 |
0.1150 |
70 |
0.3462 |
0.2693 |
0.2167 |
0.1868 |
0.1508 |
0.1365 |
0.1263 |
95 |
0.3875 |
0.2999 |
0.2400 |
0.2060 |
0.1643 |
0.1483 |
0.1368 |
120 |
0.4236 |
0.3266 |
0.2603 |
0.2228 |
0.1760 |
0.1584 |
0.1460 |
150 |
0.4647 |
0.3570 |
0.2834 |
0.2418 |
0.1893 |
0.1700 |
0.1563 |
185 |
0.5059 |
0.3873 |
0.3123 |
0.2656 |
0.2060 |
0.1815 |
0.1665 |
240 |
0.5430 |
0.4290 |
0.3439 |
0.2916 |
0.2207 |
0.1972 |
0.1805 |
300 |
0.5589 |
0.4706 |
0.3755 |
0.3175 |
0.2387 |
0.2128 |
0.1745 |
400 |
0.5940 |
0.5311 |
0.4213 |
0.3551 |
0.2648 |
0.2354 |
0.2146 |
500 |
0.6167 |
0.5839 |
0.4613 |
0.3880 |
0.2876 |
0.2551 |
0.2321 |
630 |
0.6848 |
0.6481 |
0.5099 |
0.4278 |
0.3151 |
0.2789 |
0.2533 |
Inductance for single-core cable (reference value)
Nominal |
Rated voltages of cable (kV) |
||||||
3.6/6 |
6/6 |
8.7/10 |
12/20 |
18/30 |
21/35 |
26/35 |
|
Inductance mH/Km |
|||||||
25 |
0.5954 |
0.6143 |
0.6474 |
0.6621 |
0.7006 |
0.7168 |
0.7273 |
35 |
0.5753 |
0.5932 |
0.6248 |
0.6390 |
0.6762 |
0.6942 |
0.7021 |
50 |
0.5543 |
0.5711 |
0.6011 |
0.6145 |
0.6501 |
0.6675 |
0.6751 |
70 |
0.5357 |
0.5486 |
0.5765 |
0.5919 |
0.5252 |
0.6394 |
0.6467 |
95 |
0.5172 |
0.5318 |
0.5608 |
0.5726 |
0.6043 |
0.6180 |
0.6279 |
120 |
0.5059 |
0.5197 |
0.5473 |
0.5585 |
0.5891 |
0.6051 |
0.6118 |
150 |
0.4949 |
0.5079 |
0.5341 |
0.5449 |
0.5740 |
0.5895 |
0.5959 |
185 |
0.4885 |
0.5006 |
0.5252 |
0.5351 |
0.5640 |
0.5760 |
0.5839 |
240 |
0.4790 |
0.4890 |
0.5143 |
0.5216 |
0.5487 |
0.5615 |
0.5677 |
300 |
0.4749 |
0.4818 |
0.5032 |
0.5102 |
0.5376 |
0.5484 |
0.5540 |
400 |
0.4660 |
0.4702 |
0.4927 |
0.4991 |
0.5219 |
0.5343 |
0.5395 |
500 |
0.4600 |
0.4619 |
0.4848 |
0.4907 |
0.5128 |
0.5224 |
0.5272 |
630 |
0.4547 |
0.4563 |
0.4748 |
0.4827 |
0.5012 |
0.5101 |
0.5161 |
![]()


The approx weight of cable is the weight of PVC sheathed cable