| APPLICATION | This cable is used for urban networks. It can be installed aerially, in conduit, on open trays and in underground ducts. |
| VOLTAGE RATING |
8.7/10 8.7/15 kV (17.5 kV) |
| CONSTRUCTION | Conductor: Compact round stranded copper or aluminium Conductor Shield: Semi-conducting tape and /or semi-conducting cross-linked polyethylene Insulation: Cross-linked polyethylene Insulation Shield: Semi-conducting cross-linked polyethylene Shield: Copper tape shield Filler: Polypropylene (Nonhygroscopic material) Binding Tape: Polyester and/or non-woven tape (Optional: water blocking tape) Bedding: Black polyethylene (Optional: polyvinyl chloride) Armour: Galvanized steel wire or steel tape armoured Sheath: Black Polyvinylene (ST7) (Optional: Polyvinyl Chloride) |
| SPECIFICATION | IEC60502-2 |
Detailed SpecificationNon Armoured |
|||||
Nominal |
Reference |
Nominal |
Approx |
Approx weight of cable |
|
Cu |
Al |
||||
Non Armoured |
Non Armoured |
||||
mm2 |
mm |
mm |
mm |
kg/km |
kg/km |
25 |
6.0 |
4.5 |
46 |
2380 |
1901 |
35 |
7.1 |
4.5 |
49 |
2818 |
2132 |
50 |
8.4 |
4.5 |
52 |
3299 |
2405 |
70 |
10.0 |
4.5 |
56 |
4117 |
2818 |
95 |
11.7 |
4.5 |
59 |
5155 |
3294 |
120 |
13.1 |
4.5 |
64 |
6317 |
3892 |
150 |
14.6 |
4.5 |
68 |
7303 |
4366 |
185 |
16.2 |
4.5 |
72 |
8405 |
4880 |
240 |
18.4 |
4.5 |
77 |
10323 |
5728 |
300 |
20.6 |
4.5 |
82 |
12658 |
6691 |
400 |
23.6 |
4.5 |
89 |
15195 |
7767 |
500 |
26.6 |
4.5 |
96 |
18305 |
9020 |
Steel Tape Armoured |
|||||
Nominal |
Reference |
Nominal |
Approx |
Approx weight of cable |
|
Cu |
Al |
||||
Steel Tape Armoured |
Steel Tape Armoured |
||||
mm2 |
mm |
mm |
mm |
kg/km |
kg/km |
25 |
6.0 |
4.5 |
50 |
3406 |
2929 |
35 |
7.1 |
4.5 |
53 |
3896 |
3210 |
50 |
8.4 |
4.5 |
56 |
4441 |
3547 |
70 |
10.0 |
4.5 |
59 |
5342 |
4042 |
95 |
11.7 |
4.5 |
64 |
6557 |
4697 |
120 |
13.1 |
4.5 |
69 |
7896 |
5471 |
150 |
14.6 |
4.5 |
73 |
8971 |
6033 |
185 |
16.2 |
4.5 |
76 |
10179 |
6654 |
240 |
18.4 |
4.5 |
82 |
12272 |
7676 |
300 |
20.6 |
4.5 |
88 |
15673 |
9706 |
400 |
23.6 |
4.5 |
96 |
18830 |
11402 |
500 |
26.6 |
4.5 |
104 |
22267 |
12982 |
Steel Wire Armoured |
|||||
Nominal |
Reference |
Nominal |
Approx |
Approx weight of cable |
|
Cu |
Al |
||||
Steel Wire Armoured |
Steel Wire Armoured |
||||
mm2 |
mm |
mm |
mm |
kg/km |
kg/km |
25 |
6.0 |
4.5 |
55 |
6203 |
5719 |
35 |
7.1 |
4.5 |
59 |
6824 |
6132 |
50 |
8.4 |
4.5 |
61 |
8195 |
7291 |
70 |
10.0 |
4.5 |
65 |
8713 |
7401 |
95 |
11.7 |
4.5 |
69 |
10085 |
8208 |
120 |
13.1 |
4.5 |
74 |
11720 |
9273 |
150 |
14.6 |
4.5 |
78 |
12915 |
9951 |
185 |
16.2 |
4.5 |
82 |
14487 |
10931 |
240 |
18.4 |
4.5 |
87 |
16828 |
12231 |
300 |
20.6 |
4.5 |
92 |
19689 |
13668 |
400 |
23.6 |
4.5 |
103 |
22440 |
15160 |
500 |
26.6 |
4.5 |
110 |
25961 |
16874 |
Continuous Current CapacityType |
XLPE Insulated Unarmoured |
XLPE Insulated Armoured |
||||||
Arrange type |
Delta (connect each other) |
Flat (the space between adjacent cores is the |
||||||
Laying method Nominal cross- |
in air |
direct buried |
in air |
direct buried |
||||
Cu |
Al |
Cu |
Al |
Cu |
Al |
Cu |
Al |
|
3 x 25 |
120 |
96 |
135 |
105 |
120 |
90 |
135 |
105 |
3 x 35 |
150 |
115 |
160 |
125 |
145 |
110 |
160 |
125 |
3 x 50 |
175 |
135 |
190 |
150 |
170 |
130 |
190 |
150 |
3 x 70 |
220 |
170 |
235 |
185 |
210 |
165 |
235 |
185 |
3 x 95 |
265 |
205 |
285 |
220 |
265 |
200 |
285 |
220 |
3 x 120 |
305 |
235 |
320 |
250 |
300 |
235 |
320 |
250 |
3 x 150 |
350 |
270 |
365 |
280 |
340 |
265 |
365 |
280 |
3 x 185 |
395 |
310 |
410 |
320 |
390 |
305 |
410 |
320 |
3 x 240 |
465 |
365 |
475 |
370 |
455 |
355 |
475 |
370 |
3 x 300 |
530 |
415 |
535 |
420 |
520 |
410 |
535 |
420 |
3 x 400 |
615 |
485 |
605 |
480 |
600 |
475 |
605 |
480 |
Ambient Temperature ˚C |
40°C |
25°C |
40°C |
25°C |
||||
Operating Temperature ˚C |
90°C |
|||||||
Technical PropertiesMain Technical Properties
No |
Uo/U (kV) Rated Voltage Technical properties |
3.6/6 |
6/6 |
8.7/10 |
12/20 |
18/30 |
21/35 |
26/35 |
1 |
Conductor DC resistance (Ω/km) See next |
See next table |
||||||
2 |
Routine partial discharge test |
5 |
||||||
3 |
Routine AC. Voltage test |
12.6/5 |
21/5 |
30.5/5 |
42/5 |
63/5 |
73.5/5 |
91/5 |
4 |
Power frequency AC voltage test |
14.4 |
24 |
34.8 |
48 |
72 |
84 |
104 |
5 |
Hot Set Test |
130 |
||||||
6 |
Hot impact resistance test (kV) |
60 |
75 |
95 |
125 |
170 |
200 |
250 |
7 |
Other tests |
See Q / 320481LL019 - 2003 |
||||||
Conductor DC Resistance
Nominal cross-sectional area 20°C, the D.C. resistance |
25 |
35 |
50 |
70 |
95 |
120 |
150 |
185 |
Cu |
0.727 |
0.524 |
0.387 |
0.268 |
0.193 |
0.153 |
0.124 |
0.0991 |
Al |
1.20 |
0.868 |
0.641 |
0.443 |
0.320 |
0.253 |
0.206 |
0.164 |
Nominal cross-sectional area 20°C, the D.C. resistance |
240 |
300 |
400 |
500 |
630 |
800 |
1000 |
Cu |
0.0754 |
0.0601 |
0.0470 |
0.0366 |
0.0283 |
0.0221 |
0.0176 |
Al |
0.125 |
0.100 |
0.0778 |
0.0605 |
0.0469 |
0.0367 |
0.0291 |
Correction coefficient of current-carrying capacity under different ambient temperature
Operating temperature |
Ambient temperature (in air) (°C) |
||||||||
10 |
15 |
20 |
25 |
30 |
35 |
40 |
45 |
50 |
|
60 |
1.58 |
1.50 |
1.41 |
1.32 |
1.22 |
1.11 |
1.00 |
0.86 |
0.73 |
65 |
1.48 |
1.41 |
1.34 |
1.26 |
1.18 |
1.09 |
1.00 |
0.89 |
0.77 |
70 |
1.41 |
1.35 |
1.29 |
1.22 |
1.15 |
1.08 |
1.00 |
0.91 |
0.81 |
80 |
1.32 |
1.27 |
1.22 |
1.17 |
1.11 |
1.06 |
1.00 |
0.93 |
0.86 |
90 |
1.26 |
1.22 |
1.18 |
1.14 |
1.09 |
1.04 |
1.00 |
0.94 |
0.89 |
105 |
1.22 |
1.19 |
1.15 |
1.11 |
1.08 |
1.04 |
1.00 |
0.95 |
0.91 |
Operating temperature |
Ambient temperature (in soil) (°C) |
|||||
10 |
15 |
20 |
25 |
30 |
35 |
|
60 |
1.20 |
1.13 |
1.07 |
1.00 |
0.93 |
0.85 |
65 |
1.17 |
1.12 |
1.06 |
1.00 |
0.94 |
0.87 |
70 |
1.15 |
1.11 |
1.05 |
1.00 |
0.94 |
0.88 |
80 |
1.13 |
1.09 |
1.04 |
1.00 |
0.95 |
0.90 |
90 |
1.11 |
1.07 |
1.04 |
1.00 |
0.96 |
0.92 |
Correction coefficient of current-carrying capacity for different specific thermal resistivity of ground
Voltage |
Sectional area |
Specific thermal resistivity of ground ρ t (K.m/W) |
||||
(kV) |
(mm²) |
0.8 |
1.0 |
1.2 |
1.5 |
2.0 |
3.6/6 ~ 6/6 |
≤35 |
1.06 |
1.00 |
0.95 |
0.88 |
0.80 |
6/10 ~ 12/15 |
≤35 |
1.05 |
1.00 |
0.95 |
0.89 |
0.80 |
12/20 ~ 26/35 |
≤95 |
1.05 |
1.00 |
0.95 |
0.90 |
0.82 |
Correction coefficient of current rating capacity for multi - cables laid in parallel in air
Array |
Layer no. |
Layers x Pcs |
Gap between cable/cable Dia. |
Correction factor |
Note |
|
Plane parallel |
Level |
Vertical |
||||
One layer |
1 x 2 |
- |
< 5 |
0.89 |
d = Gap between cables |
|
1 x 3 |
- |
< 0.75 |
0.84 |
|||
Two layers |
2 x 1 |
< 0.5 |
1.9~1.5 |
0.99 |
||
1.4~1.0 |
0.97 |
|||||
< 0.5 |
0.90 |
|||||
2 x 2 |
< 0.5 |
2~1.5 |
0.99 |
|||
1.49~1.5 |
0.97 |
|||||
0.9~0.5 |
0.90 |
|||||
Three layers |
3 x 1 |
- |
4~3 |
0.99 |
||
2.9~2.0 |
0.97 |
|||||
1.9~1.0 |
0.94 |
|||||
< 0.5 |
0.85 |
|||||
3 x 2 |
< 0.5 |
4~3 |
0.99 |
|||
2.9~2.0 |
0.97 |
|||||
3 x 3 |
< 0.75 |
1.9~1.0 |
0.94 |
|||
< 0.5 |
0.85 |
|||||
Max. calculated permissible short - circuit for conductor
Nominal cross-section of |
Maximum permissible short-circuit for conductor (1 sec.) |
|
Maximum permissible short-circuit for conductor (1 sec.) |
Aluminium conductor |
|
10 |
1.51 |
0.988 |
16 |
2.39 |
1.56 |
25 |
3.69 |
2.42 |
35 |
5.15 |
3.37 |
50 |
7.31 |
4.79 |
70 |
10.2 |
6.68 |
95 |
13.8 |
9.03 |
120 |
17.4 |
11.4 |
150 |
21.7 |
14.2 |
185 |
26.7 |
17.5 |
240 |
34.6 |
22.6 |
300 |
43.1 |
28.2 |
400 |
57.4 |
37.6 |
500 |
71.7 |
47.0 |
630 |
88.8 |
58.0 |
Max. permissible short-circuit for current for metallic screen (copper tape screen)
Nominal |
Rated voltages of cable (kV) |
||||||
3.6/6 |
6/6 |
8.7/10 |
12/20 |
18/30 |
21/35 |
26/35 |
|
Short-Circuit Current A |
|||||||
25 |
1075 |
1083 |
1094 |
- |
- |
- |
- |
35 |
1074 |
1082 |
1092 |
1096 |
- |
- |
- |
50 |
1072 |
1080 |
1091 |
1095 |
1284 |
1286 |
1288 |
70 |
1070 |
1079 |
1090 |
1091 |
1281 |
1285 |
1286 |
95 |
1069 |
1077 |
1086 |
1272 |
1280 |
1284 |
1283 |
120 |
1068 |
1077 |
1286 |
1271 |
1279 |
1280 |
1282 |
150 |
1067 |
1076 |
1265 |
1270 |
1278 |
1279 |
1282 |
185 |
1064 |
1251 |
1264 |
1267 |
1275 |
1276 |
1279 |
240 |
1241 |
1250 |
1262 |
1266 |
1274 |
1275 |
1278 |
300 |
1239 |
1246 |
1261 |
1265 |
1270 |
1272 |
1277 |
400 |
1240 |
1245 |
1256 |
1260 |
1270 |
1272 |
1274 |
500 |
1243 |
1244 |
1253 |
1257 |
1266 |
1272 |
1273 |
630 |
1236 |
1238 |
1252 |
1253 |
1265 |
1270 |
1270 |
Capacitance of cable (reference value)
Nominal |
Rated voltages of cable (kV) |
||||||
3.6/6 |
6/6 |
8.7/10 |
12/20 |
18/30 |
21/35 |
26/35 |
|
Capacitance for each phase μ F/Km |
|||||||
25 |
0.2423 |
0.1922 |
0.1576 |
0.1378 |
0.1163 |
0.1064 |
0.0992 |
35 |
0.2684 |
0.1922 |
0.1725 |
0.1502 |
0.1251 |
0.1140 |
0.1061 |
50 |
0.3022 |
0.2367 |
0.1917 |
0.1661 |
0.1363 |
0.1239 |
0.1150 |
70 |
0.3462 |
0.2693 |
0.2167 |
0.1868 |
0.1508 |
0.1365 |
0.1263 |
95 |
0.3875 |
0.2999 |
0.2400 |
0.2060 |
0.1643 |
0.1483 |
0.1368 |
120 |
0.4236 |
0.3266 |
0.2603 |
0.2228 |
0.1760 |
0.1584 |
0.1460 |
150 |
0.4647 |
0.3570 |
0.2834 |
0.2418 |
0.1893 |
0.1700 |
0.1563 |
185 |
0.5059 |
0.3873 |
0.3123 |
0.2656 |
0.2060 |
0.1815 |
0.1665 |
240 |
0.5430 |
0.4290 |
0.3439 |
0.2916 |
0.2207 |
0.1972 |
0.1805 |
300 |
0.5589 |
0.4706 |
0.3755 |
0.3175 |
0.2387 |
0.2128 |
0.1745 |
400 |
0.5940 |
0.5311 |
0.4213 |
0.3551 |
0.2648 |
0.2354 |
0.2146 |
500 |
0.6167 |
0.5839 |
0.4613 |
0.3880 |
0.2876 |
0.2551 |
0.2321 |
630 |
0.6848 |
0.6481 |
0.5099 |
0.4278 |
0.3151 |
0.2789 |
0.2533 |
Inductance for three-core cable (reference value)
Nominal |
Rated voltages of cable (kV) |
||||||
3.6/6 |
6/6 |
8.7/10 |
12/20 |
18/30 |
21/35 |
26/35 |
|
Inductance mH/Km |
|||||||
25 |
0.3552 |
0.3797 |
0.4061 |
- |
- |
- |
- |
35 |
0.3384 |
0.3613 |
0.3862 |
0.4064 |
- |
- |
- |
50 |
0.3211 |
0.3423 |
0.3655 |
0.3845 |
0.4396 |
0.4396 |
0.4679 |
70 |
0.3040 |
0.3232 |
0.3445 |
0.3620 |
0.4145 |
0.4145 |
0.4427 |
95 |
0.2915 |
0.3092 |
0.3290 |
0.3454 |
0.3956 |
0.3956 |
0.4208 |
120 |
0.2826 |
0.2992 |
0.3178 |
0.3392 |
0.3799 |
0.3799 |
0.4019 |
150 |
0.2742 |
0.2897 |
0.3071 |
0.3217 |
0.3642 |
0.3642 |
0.3862 |
185 |
0.2672 |
0.2817 |
0.3009 |
0.3145 |
0.3485 |
0.3485 |
0.3737 |
240 |
0.2608 |
0.2726 |
0.2904 |
0.3030 |
0.3360 |
0.3360 |
0.3611 |
300 |
0.2576 |
0.2651 |
0.2817 |
0.2935 |
0.3266 |
0.3266 |
0.3485 |
400 |
0.2516 |
0.2564 |
0.2714 |
0.2822 |
0.3041 |
0.3041 |
0.3266 |
500 |
0.2480 |
0.2503 |
0.2641 |
0.2742 |
- |
- |
- |
630 |
0.2421 |
0.2442 |
- |
- |
- |
- |
- |
![]()


The approx weight of cable is the weight of PVC sheathed cable