| APPLICATION | This cable is mainly used in power stations, mass transit underground passenger systems, airports, petrochemical plants, hotels, hospitals, and high-rise buildings. |
| VOLTAGE RATING |
600/1000V |
| CONSTRUCTION | Plain annealed copper, XLPE or XLEVA compound insulated, unarmoured or galvanized steel wires armoured, LSZH compound sheathed cable |
| INSULATION COLOUR |
|
| SHEATH COLOUR |
Black or as per order |
| SPECIFICATION | Refer BS6724, IEC60502-1, IEC60332-1, IEC60332-3, IEC60754, IEC61034 |
Detailed Specification2-CORE |
||||||||||
Conductor |
Insulation |
Unarmoured Cable |
Armoured Cable |
|||||||
Nominal Area |
No./Dia of Strand |
Thickness |
Cable Overall Diameter |
Approx. Weight |
Cable Overall Diameter |
Approx. Weight |
||||
mm2 |
No./mm |
mm |
mm |
kg/km |
mm |
kg/km |
||||
1.5 |
7/0.53 |
0.7 |
10.0 |
130 |
14.5 |
325 |
||||
2.5 |
7/0.67 |
0.7 |
11.0 |
165 |
15.5 |
400 |
||||
4 |
7/0.85 |
0.7 |
12.0 |
215 |
16.5 |
475 |
||||
6 |
7/1.04 |
0.7 |
13.0 |
270 |
18.0 |
570 |
||||
10 |
7/1.35 |
0.7 |
15.0 |
390 |
20.0 |
710 |
||||
16 |
7/1.70 |
0.7 |
17.0 |
550 |
22.0 |
1040 |
||||
25 |
7/2.14 |
0.9 |
20.4 |
670 |
26.0 |
1350 |
||||
35 (s) |
19/1.53 |
0.9 |
22.7 |
880 |
23.5 |
1510 |
||||
3-CORE |
||||||||||
Conductor |
Insulation |
Unarmoured Cable |
Armoured Cable |
|||||||
Nominal Area |
No./Dia of Strand |
Thickness |
Cable Overall Diameter |
Approx. Weight |
Cable Overall Diameter |
Approx. Weight |
||||
mm2 |
No./mm |
mm |
mm |
kg/km |
mm |
kg/km |
||||
1.5 |
7/0.53 |
0.7 |
10.5 |
150 |
15.0 |
375 |
||||
2.5 |
7/0.67 |
0.7 |
11.4 |
195 |
16.0 |
400 |
||||
4 |
7/0.85 |
0.7 |
12.5 |
260 |
17.0 |
520 |
||||
6 |
7/1.04 |
0.7 |
14.0 |
320 |
18.0 |
640 |
||||
10 |
7/1.35 |
0.7 |
16.0 |
470 |
20.0 |
860 |
||||
16 |
7/1.70 |
0.7 |
18.0 |
680 |
23.0 |
1220 |
||||
25 (s) |
12/1.70 |
0.9 |
19.8 |
950 |
24.8 |
1630 |
||||
35 (s) |
19/1.53 |
0.9 |
21.5 |
1260 |
26.5 |
2050 |
||||
50 (s) |
19/1.78 |
1.0 |
25.5 |
1670 |
30.5 |
2590 |
||||
70 (s) |
19/.2.14 |
1.1 |
29.0 |
2340 |
35.8 |
3600 |
||||
95 (s) |
19/2.52 |
1.1 |
32.0 |
3150 |
38.5 |
4590 |
||||
120 (s) |
37/2.03 |
1.2 |
35.7 |
3930 |
42.5 |
5560 |
||||
150 (s) |
37/2.25 |
1.4 |
40.5 |
4830 |
47.5 |
6920 |
||||
185 (s) |
37/2.52 |
1.6 |
45.0 |
6050 |
52.0 |
8530 |
||||
240 (s) |
61/2.25 |
1.7 |
53.5 |
8080 |
61.0 |
10900 |
||||
300 (s) |
61/2.52 |
1.8 |
60.0 |
10070 |
68.0 |
13225 |
||||
400 (s) |
61/2.85 |
2.0 |
65.5 |
12770 |
73.0 |
16200 |
||||
4-CORE |
||||||||||
Conductor |
Insulation |
Unarmoured Cable |
Armoured Cable |
|||||||
Nominal Area |
No./Dia of Strand |
Thickness |
Cable Overall Diameter |
Approx. Weight |
Cable Overall Diameter |
Approx. Weight |
||||
mm2 |
No./mm |
mm |
mm |
kg/km |
mm |
kg/km |
||||
1.5 |
7/0.53 |
0.7 |
11.5 |
180 |
15.5 |
410 |
||||
2.5 |
7/0.67 |
0.7 |
12.5 |
230 |
16.5 |
495 |
||||
4 |
7/0.85 |
0.7 |
14.0 |
315 |
18.0 |
610 |
||||
6 |
7/1.04 |
0.7 |
15.5 |
395 |
20.0 |
810 |
||||
10 |
1/1.35 |
0.7 |
17.5 |
590 |
22.7 |
1120 |
||||
16 |
7/1.70 |
0.7 |
20.0 |
860 |
26.0 |
1480 |
||||
25 (s) |
12/1.70 |
0.9 |
21.5 |
1225 |
27.0 |
1980 |
||||
35 (s) |
19/1.53 |
0.9 |
25.0 |
1625 |
30.4 |
2480 |
||||
50 (s) |
19/1.78 |
1.0 |
28.0 |
2200 |
33.0 |
3180 |
||||
70 (s) |
19/2.14 |
1.1 |
32.0 |
3050 |
38.5 |
4500 |
||||
95 (s) |
19/2.52 |
1.1 |
37.0 |
4110 |
43.0 |
5775 |
||||
120 (s) |
37/2.03 |
1.2 |
42.0 |
5915 |
49.0 |
7450 |
||||
150 (s) |
37/2.25 |
1.4 |
46.0 |
6350 |
53.0 |
8830 |
||||
185 (s) |
37/2.52 |
1.6 |
50.5 |
7985 |
58.0 |
10805 |
||||
240 (s) |
61/2.25 |
1.7 |
58.0 |
10595 |
65.0 |
13630 |
||||
300 (s) |
61/2.52 |
1.8 |
64.0 |
13220 |
71.5 |
16530 |
||||
400 (s) |
61/2.85 |
2.0 |
73.0 |
16805 |
78.1 |
21840 |
||||
Current Rating and Voltage DropMulti-Core Cables with XLPE (or LSZH) Insulation, PVC (or LSZH) Outsheath 300/500V or 600/1000V
Current-Carrying Capacities (Amp) [CU/XLPE/PVC or CU/XLPE/LSZH cables]
| Conductor Operating Temperature : 90°C | BS 7211 |
| Ambient Temperature : 30°C | IEC60502-1 |
Conductor cross-sectional area |
Reference Method 4 (enclosed in an conduit insulated wall etc) |
Reference Method 3 |
Reference Method 1 (clipped direct) |
Reference Method 11 |
|||
one 3-core cable or one 4-core cable 3-phase a.c. |
one 2-core cable singlephase a.c. or d.c. |
one 3-core cable or one 4-core cable 3-phase a.c. |
one 2-core cable singlephase a.c. or d.c. |
one 3-core cable or one 4-core cable 3-phase a.c. |
one 2-core |
one 3-core |
|
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
mm2 |
A |
A |
A |
A |
A |
A |
A |
1.5 |
16.5 |
22 |
19.5 |
24 |
22 |
26 |
23 |
2.5 |
22 |
30 |
26 |
33 |
30 |
36 |
32 |
4 |
30 |
40 |
35 |
45 |
40 |
49 |
42 |
6 |
38 |
51 |
44 |
58 |
52 |
63 |
54 |
10 |
51 |
69 |
60 |
80 |
71 |
86 |
75 |
16 |
68 |
91 |
80 |
107 |
96 |
115 |
100 |
25 |
89 |
119 |
105 |
138 |
119 |
149 |
127 |
35 |
109 |
146 |
128 |
171 |
147 |
185 |
158 |
50 |
130 |
175 |
154 |
209 |
179 |
225 |
192 |
70 |
164 |
221 |
194 |
269 |
229 |
289 |
246 |
95 |
197 |
265 |
233 |
328 |
278 |
352 |
298 |
120 |
227 |
305 |
268 |
382 |
322 |
410 |
346 |
150 |
259 |
334 |
300 |
441 |
371 |
473 |
399 |
185 |
295 |
384 |
340 |
506 |
424 |
542 |
456 |
240 |
346 |
459 |
398 |
599 |
500 |
641 |
538 |
300 |
396 |
532 |
455 |
693 |
576 |
741 |
621 |
400 |
- |
625 |
536 |
803 |
667 |
865 |
741 |
Voltage Drop (Per Amp Per Meter) [CU/XLPE/PVC or CU/XLPE/LSZH cables]
| Conductor Operating Temperature : 90°C | BS 7211 |
| Ambient Temperature : 30°C | IEC60502-1 |
Conductor cross-sectional area |
2-core cable d.c. |
2-core cable single-phase a.c |
3-core or 4-core cable 3-phase a.c. |
||||
1 |
2 |
3 |
4 |
||||
mm2 |
mV/A/m |
mV/A/m |
mV/A/m |
||||
1.5 |
31 |
|
31 |
|
|
27 |
|
2.5 |
19 |
|
19 |
|
|
16 |
|
4 |
12 |
|
12 |
|
|
10 |
|
6 |
7.9 |
|
7.9 |
|
|
6.8 |
|
10 |
4.7 |
|
4.7 |
|
|
4.0 |
|
16 |
2.9 |
|
2.9 |
|
|
2.5 |
|
|
|
r |
x |
z |
r |
x |
z |
25 |
1.85 |
1.85 |
0.16 |
1.90 |
1.6 |
0.14 |
1.65 |
35 |
1.35 |
1.35 |
0.155 |
1.35 |
1.15 |
0.135 |
1.15 |
50 |
0.98 |
0.99 |
0.155 |
1.00 |
0.86 |
0.135 |
0.87 |
70 |
0.67 |
0.67 |
0.150 |
0.69 |
0.59 |
0.130 |
0.60 |
95 |
0.49 |
0.50 |
0.150 |
0.52 |
0.43 |
0.130 |
0.45 |
120 |
0.39 |
0.40 |
0.145 |
0.42 |
0.34 |
0.130 |
0.37 |
150 |
0.31 |
0.32 |
0.145 |
0.35 |
0.28 |
0.125 |
0.30 |
185 |
0.25 |
0.26 |
0.145 |
0.29 |
0.22 |
0.125 |
0.26 |
240 |
0.195 |
0.20 |
0.140 |
0.24 |
0.175 |
0.125 |
0.21 |
300 |
0.155 |
0.16 |
0.140 |
0.21 |
0.140 |
0.120 |
0.185 |
400 |
0.120 |
0.13 |
0.140 |
0.19 |
0.115 |
0.120 |
0.165 |
Multi-Core Cables with XLPE (or LSZH) Insulation, Armoured, PVC or LSZH Outsheath 600/1000V
Current-Carrying Capacities (Amp) [CU/XLPE/SWA/PVC or CU/XLPE/SWA/LSZH Cables]
| BS 6724 | |
| Conductor Operating Temperature : 90°C | BS 7846 |
| Ambient Temperature : 30°C | IEC60502-1 |
Conductor |
Reference Method 1 (clipped |
Reference Method 11 (on a |
In single-way ducts |
Laid direct in ground |
||||
|
one 2-core cable single phase a.c. or d.c. |
one 3-core or 4-core cable 3-phase a.c. |
one 2-core cable single phase a.c. or d.c. |
one 3-core or 4-core cable 3-phase a.c. |
one 2-core cable single phase a.c. or d.c. |
one 3-core or 4-core cable 3-phase a.c. |
one 2-core cable single phase a.c. or d.c. |
one 3-core or 4-core cable 3-phase a.c. |
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
mm2 |
A |
A |
A |
A |
A |
A |
A |
A |
1.5 |
27 |
23 |
29 |
25 |
- |
23 |
- |
28 |
2.5 |
36 |
31 |
39 |
33 |
- |
30 |
- |
36 |
4 |
49 |
42 |
52 |
44 |
- |
40 |
- |
48 |
6 |
62 |
53 |
66 |
56 |
- |
50 |
- |
60 |
10 |
85 |
73 |
90 |
78 |
- |
65 |
- |
80 |
16 |
110 |
94 |
115 |
99 |
115 |
94 |
140 |
115 |
25 |
146 |
124 |
152 |
131 |
145 |
125 |
180 |
150 |
35 |
180 |
154 |
188 |
162 |
175 |
150 |
215 |
180 |
50 |
219 |
187 |
228 |
197 |
210 |
175 |
255 |
215 |
70 |
279 |
238 |
291 |
251 |
260 |
215 |
315 |
265 |
95 |
338 |
289 |
354 |
304 |
310 |
260 |
380 |
315 |
120 |
392 |
335 |
410 |
353 |
355 |
300 |
430 |
360 |
150 |
451 |
386 |
472 |
406 |
400 |
335 |
480 |
405 |
185 |
515 |
441 |
539 |
463 |
455 |
380 |
540 |
460 |
240 |
607 |
520 |
636 |
546 |
520 |
440 |
630 |
530 |
300 |
698 |
599 |
732 |
628 |
590 |
495 |
700 |
590 |
400 |
787 |
673 |
847 |
728 |
660 |
560 |
790 |
670 |
Voltage Drop (Per Amp Per Meter) [CU/XLPE/SWA/PVC or CU/XLPE/SWA/LSZH Cables
| BS 6724 | |
| Conductor Operating Temperature : 90°C | BS 7846 |
| Ambient Temperature : 30°C | IEC60502-1 |
Conductor |
2-core cable d.c. |
2 cables, single-phase a.c. |
3 or 4 cables, 3-phase a.c. |
2 cables, |
3 or 4 cables, |
||||
In ducts or |
In ducts or |
||||||||
1 |
2 |
3 |
4 |
5 |
6 |
||||
mm2 |
mV/A/m |
mV/A/m |
mV/A/m |
mV/A/m |
mV/A/m |
||||
1.5 |
31.0 |
|
31.0 |
|
|
27.0 |
|
31.0 |
25.0 |
2.5 |
19.0 |
|
19.0 |
|
|
16.0 |
|
19.0 |
15.0 |
4 |
12.0 |
|
12.0 |
|
|
10.0 |
|
12.0 |
9.7 |
6 |
7.9 |
|
7.9 |
|
|
6.8 |
|
7.9 |
6.5 |
10 |
4.7 |
|
4.7 |
|
|
4.0 |
|
4.7 |
3.9 |
16 |
2.9 |
|
2.9 |
|
|
2.5 |
|
2.9 |
2.6 |
|
|
r |
x |
z |
r |
x |
z |
|
|
25 |
1.850 |
1.350 |
0.160 |
1.900 |
1.600 |
0.140 |
1.650 |
1.900 |
1.600 |
35 |
1.350 |
1.350 |
0.155 |
1.350 |
1.150 |
0.135 |
1.150 |
1.350 |
1.200 |
50 |
0.980 |
0.990 |
0.155 |
1.000 |
0.860 |
0.135 |
0.870 |
1.000 |
0.870 |
70 |
0.670 |
0.670 |
0.150 |
0.690 |
0.590 |
0.130 |
0.600 |
0.690 |
0.610 |
95 |
0.490 |
0.500 |
0.150 |
0.520 |
0.430 |
0.130 |
0.450 |
0.520 |
0.450 |
120 |
0.390 |
0.400 |
0.145 |
0.420 |
0.340 |
0.130 |
0.370 |
0.420 |
0.360 |
150 |
0.310 |
0.320 |
0.145 |
0.350 |
0.280 |
0.125 |
0.300 |
0.350 |
0.300 |
185 |
0.250 |
0.260 |
0.145 |
0.290 |
0.220 |
0.125 |
0.260 |
0.290 |
0.250 |
240 |
0.195 |
0.200 |
0.140 |
0.240 |
0.175 |
0.125 |
0.210 |
0.240 |
0.210 |
300 |
0.155 |
0.160 |
0.140 |
0.210 |
0.140 |
0.120 |
0.185 |
0.210 |
0.190 |
400 |
0.120 |
0.130 |
0.140 |
0.190 |
0.115 |
0.120 |
0.165 |
0.190 |
0.180 |