| APPLICATION | It must be laide pipes at sight,embedded or closed system, allowed for fixed and protected installation,upon or into illumination sets for voltage under 1000V AC or 750V DC to ground. |
| VOLTAGE RATING |
300/500V or 450/750V |
| CONSTRUCTION | Bare or tinned copper conductor according to DIN VDE 0295 and IEC 60228 class 5,EI5 or TI1 insulated |
| INSULATION COLOUR |
Black,Light Blue,Brown,Grey,Orange,Pink,Red,Turquoise,Violet White,Green/Yellow |
| SPECIFICATION | Generally to EN50265 HD21.3S3 |
Detailed SpecificationH05Z-K & H05V-K |
||||||||||
Conductor |
Insulation |
Approx. Diameter of Cable |
Approx. Cable Weight |
|||||||
NO.of core |
Nominal Area |
Approx. Diameter |
Thickness |
|||||||
|
mm2 |
mm |
mm |
mm |
kg/km |
|||||
Single core |
0.40 |
0.77 |
0.6 |
2.3 |
7 |
|||||
0.75 |
0.95 |
0.6 |
2.4 |
10 |
||||||
1.0 |
1.30 |
0.6 |
2.6 |
12 |
||||||
H07Z-K & H07V-K |
||||||||||
Conductor |
Insulation |
Approx. Diameter of Cable |
Approx. Cable Weight |
|||||||
NO.of core |
Nominal Area |
Approx. Diameter |
Thickness |
|||||||
|
mm2 |
mm |
mm |
mm |
kg/km |
|||||
Single core |
1.5 |
1.6 |
0.7 |
3.1 |
21 |
|||||
2.5 |
2 |
0.8 |
3.8 |
33 |
||||||
4 |
2.6 |
0.8 |
4.4 |
48 |
||||||
6 |
3.4 |
0.8 |
4.9 |
66 |
||||||
10 |
44 |
1.0 |
6.4 |
112 |
||||||
16 |
5.7 |
1.0 |
7.4 |
167 |
||||||
25 |
6.9 |
1.2 |
9.1 |
254 |
||||||
35 |
8.1 |
1.2 |
10.4 |
340 |
||||||
50 |
9.8 |
1.4 |
12.4 |
485 |
||||||
70 |
11.6 |
1.4 |
13.6 |
674 |
||||||
95 |
13.3 |
1.6 |
15.8 |
894 |
||||||
120 |
15.1 |
1.6 |
17.4 |
1110 |
||||||
150 |
16.8 |
1.8 |
19.8 |
1400 |
||||||
185 |
18.8 |
2.0 |
21.6 |
1700 |
||||||
240 |
21.4 |
2.2 |
24.6 |
2230 |
||||||
Current Rating and Voltage DropFlexible Cables with PVC Insulation, or PVC Insulation & PVC Outsheath
Technical Data Flexible Cord, Imperial Sizes (CU/PVC or CU/PVC/PVC)
| Conductor Operating Temperature : 90°C | BS 2004 |
| Ambient Temperature : 30°C |
Conductor |
Current Rating |
Voltage Drop per 100 feet |
Maximum Weight |
||
Nominal Area |
Construction |
1 or 3 phase a.c. or d.c. |
d.c. or 1 phase a.c. |
3 phase a.c. |
|
in2 |
No. / in |
Amp |
V |
V |
lb |
0.0006 |
14 / 0.0076 |
3 |
8.9 |
7.7 |
3 |
0.0010 |
23 / 0.0076 |
6 |
11 |
9.4 |
5 |
0.0017 |
40 / 0.0076 |
13 |
14 |
12 |
10 |
0.0030 |
70 / 0.0076 |
18 |
12 |
10 |
10 |
0.0048 |
110 / 0.0076 |
24 |
9.6 |
8.3 |
10 |
0.0070 |
162 / 0.0076 |
31 |
8.4 |
7.3 |
10 |
Technical Data Flexible Cord, Imperial Sizes (CU/PVC or CU/PVC/PVC)
| Conductor Operating Temperature : 90°C | BS 6500 |
| Ambient Temperature : 30°C |
Conductor |
Current Rating |
Voltage Drop per 100 feet |
Maximum Weight |
||
Nominal Area |
Construction |
1 or 3 phase a.c. or d.c. |
d.c. or 1 phase a.c. |
3 phase a.c. |
|
mm2 |
No. / mm |
Amp |
mV/m |
mV/m |
Kg |
0.50 |
16/0.2 |
3 |
83 |
72 |
2 |
0.75 |
24/0.2 |
6 |
56 |
48 |
3 |
1.00 |
32/0.2 |
10 |
43 |
37 |
5 |
1.25 |
40/0.2 |
13 |
35 |
29 |
5 |
1.50 |
30/0.25 |
16 |
31 |
26 |
5 |
2.50 |
50/0.25 |
25 |
18 |
16 |
5 |
4.00 |
56/0.30 |
32 |
11 |
10 |
5 |
![]()