| APPLICATION | This cable is primarily used for main power supply. It can be installed in cable ducts, on cable trays, on cable ladders and in cable trunking. The armoured cable is ideal for ground emplacement if a higher electrical or mechanical protection is required. |
| VOLTAGE RATING |
600/1000V |
| CONSTRUCTION | Plain annealed copper, PVC insulated, unarmoured or galvanized steel wires armoured, PVC sheathed cable |
| INSULATION COLOUR |
|
| SHEATH COLOUR |
Black |
| SPECIFICATION | BS6346, IEC60502-1 |
Detailed Specification2-CORE |
|||||||||
Conductor |
Insulation |
Unarmoured Cable |
Armoured Cable |
||||||
Nominal Area |
Thickness |
Approx. Overall Diameter |
Approx. Cable Weight |
Approx. Overall Diameter |
Approx. Cable Weight |
||||
mm2 |
mm |
mm |
kg/km |
mm |
kg/km |
||||
1.5 (cs) |
0.8 |
11.2 |
150 |
12.1 |
290 |
||||
2.5 (cs) |
0.8 |
11.6 |
180 |
13.3 |
340 |
||||
4 (cs) |
1.0 |
13.7 |
260 |
15.4 |
470 |
||||
6 (cs) |
1.0 |
15.2 |
290 |
16.8 |
550 |
||||
10 (cs) |
1.0 |
16.1 |
450 |
20.8 |
860 |
||||
16 (cs) |
1.0 |
18.2 |
550 |
22.1 |
1080 |
||||
25 (s) |
1.2 |
19.0 |
680 |
23.0 |
1440 |
||||
35 (s) |
1.2 |
21.0 |
940 |
25.0 |
1600 |
||||
50 (s) |
1.4 |
23.0 |
1250 |
28.0 |
1990 |
||||
70 (s) |
1.4 |
26.0 |
1700 |
30.6 |
2550 |
||||
95 (s) |
1.6 |
29.3 |
2330 |
35.8 |
3630 |
||||
120 (s) |
1.6 |
31.8 |
2860 |
38.3 |
4220 |
||||
150 (s) |
1.8 |
35.1 |
3550 |
41.5 |
5020 |
||||
185 (s) |
2.0 |
39.1 |
4360 |
46.4 |
6530 |
||||
240 (s) |
2.2 |
43.9 |
5550 |
51.2 |
8190 |
||||
300 (s) |
2.4 |
48.7 |
6910 |
56.4 |
9860 |
||||
400 (s) |
2.6 |
54.2 |
8600 |
61.9 |
11190 |
||||
3-CORE |
|||||||||
Conductor |
Insulation |
Unarmoured Cable |
Armoured Cable |
||||||
Nominal Area |
Thickness |
Approx. Overall Diameter |
Approx. Cable Weight |
Approx. Overall Diameter |
Approx. Cable Weight |
||||
mm2 |
mm |
mm |
kg/km |
mm |
kg/km |
||||
1.5 (cs) |
0.8 |
11.3 |
165 |
12.9 |
305 |
||||
2.5 (cs) |
0.8 |
12.3 |
200 |
14.4 |
390 |
||||
4 (cs) |
1.0 |
14.2 |
300 |
16.0 |
520 |
||||
6 (cs) |
1.0 |
15.8 |
380 |
18.1 |
705 |
||||
10 (cs) |
1.0 |
17.0 |
545 |
21.1 |
945 |
||||
16 (cs) |
1.0 |
19.7 |
760 |
23.5 |
1220 |
||||
25 (s) |
1.2 |
21.0 |
955 |
26.0 |
1700 |
||||
35 (s) |
1.2 |
23.0 |
1300 |
27.0 |
2100 |
||||
50 (s) |
1.4 |
26.5 |
1720 |
31.0 |
2560 |
||||
70 (s) |
1.4 |
29.5 |
2380 |
35.0 |
3360 |
||||
95 (s) |
1.6 |
35.0 |
3245 |
39.1 |
4630 |
||||
120 (s) |
1.6 |
37.0 |
4030 |
42.1 |
5710 |
||||
150 (s) |
1.8 |
41.0 |
5000 |
47.3 |
7160 |
||||
185 (s) |
2.0 |
46.0 |
6140 |
51.9 |
8510 |
||||
240 (s) |
2.2 |
51.0 |
7960 |
57.8 |
10790 |
||||
300 (s) |
2.4 |
58.0 |
9850 |
63.2 |
12940 |
||||
400 (s) |
2.6 |
62.0 |
12990 |
69.6 |
16970 |
||||
4-CORE |
|||||||||
Conductor |
Insulation |
Unarmoured Cable |
Armoured Cable |
||||||
Nominal Area |
Thickness |
Approx. Overall Diameter |
Approx. Cable Weight |
Approx. Overall Diameter |
Approx. Cable Weight |
||||
mm2 |
mm |
mm |
kg/km |
mm |
kg/km |
||||
1.5 (cs) |
0.8 |
12.3 |
210 |
13.5 |
345 |
||||
2.5 (cs) |
0.8 |
13.2 |
265 |
15.0 |
375 |
||||
4 (cs) |
1.0 |
15.2 |
385 |
17.5 |
690 |
||||
6 (cs) |
1.0 |
16.9 |
440 |
19.5 |
835 |
||||
10 (cs) |
1.0 |
18.6 |
675 |
22.9 |
1130 |
||||
16 (cs) |
1.0 |
21.6 |
925 |
26.5 |
1700 |
||||
25 (s) |
1.2 |
24.0 |
1320 |
28.0 |
2100 |
||||
35 (s) |
1.2 |
26.5 |
1740 |
31.0 |
2540 |
||||
50 (s) |
1.4 |
30.0 |
2300 |
35.4 |
3500 |
||||
70 (s) |
1.4 |
34.0 |
3180 |
39.2 |
4610 |
||||
95 (s) |
1.6 |
38.3 |
4370 |
44.4 |
5950 |
||||
120 (s) |
1.6 |
41.8 |
5400 |
49.1 |
7610 |
||||
150 (s) |
1.8 |
47.5 |
6550 |
53.8 |
9000 |
||||
185 (s) |
2.0 |
52.0 |
8180 |
59.2 |
10900 |
||||
240 (s) |
2.2 |
58.0 |
10700 |
66.7 |
13600 |
||||
300 (s) |
2.4 |
66.0 |
13200 |
72.0 |
16500 |
||||
400 (s) |
2.6 |
73.5 |
17100 |
81.3 |
23000 |
||||
Current Rating and Voltage DropMulti-Core Cables with PVC Insulation, Unarmoured, PVC Outsheath 600/1000V
Current-Carrying Capacities (Amp) [CU/PVC/PVC Cables]
| BS 6004 | |
| Conductor Operating Temperature : 70°C | BS 6346 |
| Ambient Temperature : 30°C | IEC60502-1 |
Conductor |
Reference Method 4 |
Reference Method 3 |
Reference Method 1 |
Reference Method 11 (on |
||||
one 2-core |
one 3-core |
one 2-core |
one 3-core |
one 2-core |
one 3-core |
one 2-core |
one 3-core |
|
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
mm2 |
A |
A |
A |
A |
A |
A |
A |
A |
1 |
11 |
10 |
13 |
11.5 |
15 |
13.5 |
17 |
14.5 |
1.5 |
14 |
13 |
16.5 |
15 |
19.5 |
17. |
5 22 |
18.5 |
2.5 |
18.5 |
17.5 |
23 |
20 |
27 |
24 |
30 |
25 |
4 |
25 |
23 |
30 |
27 |
36 |
32 |
40 |
34 |
6 |
32 |
29 |
38 |
34 |
46 |
41 |
51 |
43 |
10 |
43 |
39 |
52 |
46 |
63 |
57 |
70 |
60 |
16 |
57 |
52 |
69 |
62 |
85 |
76 |
94 |
80 |
25 |
75 |
68 |
90 |
80 |
112 |
96 |
119 |
101 |
35 |
92 |
83 |
111 |
99 |
138 |
119 |
148 |
126 |
50 |
110 |
99 |
133 |
118 |
168 |
144 |
180 |
153 |
70 |
139 |
125 |
168 |
149 |
213 |
184 |
232 |
196 |
95 |
167 |
150 |
201 |
179 |
258 |
223 |
282 |
238 |
120 |
192 |
172 |
232 |
206 |
299 |
259 |
328 |
276 |
150 |
219 |
196 |
258 |
225 |
344 |
299 |
379 |
319 |
185 |
248 |
223 |
294 |
255 |
392 |
341 |
434 |
364 |
240 |
291 |
261 |
344 |
297 |
461 |
403 |
514 |
430 |
300 |
334 |
298 |
394 |
339 |
530 |
464 |
593 |
497 |
400 |
- |
- |
470 |
402 |
634 |
557 |
715 |
597 |
Voltage Drop (Per Amp Per Meter) [PVC/PVC Cables]
| Conductor Operating Temperature : 70°C | |
| Ambient Temperature : 30°C |
Conductor |
2-core cable a.c. |
2-core cable single-phase a.c. |
3-core or 4-core cable 3-phase a.c. |
||||
1 |
2 |
3 |
4 |
||||
mm2 |
mV/A/m |
mV/A/m |
mV/A/m |
||||
1 |
44 |
|
44 |
|
|
38 |
|
1.5 |
29 |
|
29 |
|
|
25 |
|
2.5 |
18 |
|
18 |
|
|
15 |
|
4 |
11 |
|
11 |
|
|
9.5 |
|
6 |
7.3 |
|
7.3 |
|
|
6.4 |
|
10 |
4.4 |
|
4.4 |
|
|
3.8 |
|
16 |
2.8 |
|
2.8 |
|
|
2.4 |
|
|
|
r |
x |
z |
r |
x |
z |
25 |
1.75 |
1.75 |
0.170 |
1.75 |
1.50 |
0.145 |
1.50 |
35 |
1.25 |
1.25 |
0.165 |
1.25 |
1.10 |
0.145 |
1.10 |
50 |
0.93 |
0.93 |
0.165 |
0.94 |
0.80 |
0.140 |
0.81 |
70 |
0.63 |
0.63 |
0.160 |
0.65 |
0.55 |
0.140 |
0.57 |
95 |
0.46 |
0.47 |
0.155 |
0.50 |
0.41 |
0.135 |
0.43 |
120 |
0.36 |
0.38 |
0.155 |
0.41 |
0.33 |
0.135 |
0.35 |
150 |
0.29 |
0.30 |
0.155 |
0.34 |
0.26 |
0.130 |
0.29 |
185 |
0.23 |
0.25 |
0.150 |
0.29 |
0.21 |
0.130 |
0.25 |
240 |
0.180 |
0.190 |
0.150 |
0.24 |
0.165 |
0.130 |
0.21 |
300 |
0.145 |
0.155 |
0.145 |
0.21 |
0.135 |
0.130 |
0.185 |
400 |
0.105 |
0.115 |
0.145 |
0.185 |
0.100 |
0.125 |
0.160 |
Multi-Core Cables with PVC Insulation, Armoured, PVC Outsheath 600/1000V
Current-Carrying Capacities (Amp) [CU/PVC/SWA/PVC Cable]
| Conductor Operating Temperature : 70°C | BS 6346 |
| Ambient Temperature : 30°C |
Conductor cross-sectional |
Reference Method 1 (clipped |
Reference Method 11 (on a |
Direct in ground |
In single way ducts |
||||
one 2-core |
one 3-core or |
one 2-core |
one 3-core or |
2-core |
3-core or |
2-core |
3-core or |
|
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
mm2 |
A |
A |
A |
A |
A |
A |
A |
A |
1.5 |
21 |
18 |
22 |
19 |
32 |
27 |
26 |
22 |
2.5 |
28 |
25 |
31 |
26 |
41 |
35 |
34 |
29 |
4 |
38 |
33 |
41 |
35 |
55 |
47 |
45 |
38 |
6 |
49 |
42 |
53 |
45 |
69 |
59 |
57 |
48 |
10 |
67 |
58 |
72 |
62 |
92 |
78 |
76 |
64 |
16 |
89 |
77 |
97 |
83 |
119 |
101 |
98 |
83 |
25 |
118 |
102 |
128 |
110 |
158 |
132 |
129 |
107 |
35 |
145 |
125 |
157 |
135 |
190 |
159 |
154 |
126 |
50 |
175 |
151 |
190 |
163 |
225 |
188 |
183 |
153 |
70 |
222 |
192 |
241 |
207 |
277 |
233 |
225 |
190 |
95 |
269 |
231 |
291 |
251 |
332 |
279 |
271 |
228 |
120 |
310 |
267 |
336 |
290 |
377 |
317 |
309 |
260 |
150 |
356 |
306 |
386 |
332 |
422 |
355 |
346 |
292 |
185 |
405 |
348 |
439 |
378 |
478 |
401 |
393 |
331 |
240 |
476 |
409 |
516 |
445 |
551 |
462 |
455 |
382 |
300 |
547 |
469 |
592 |
510 |
616 |
517 |
510 |
428 |
400 |
621 |
540 |
683 |
590 |
693 |
580 |
574 |
490 |
Voltage Drop (Per Amp Per Meter) [PVC/PVC Cables]
| Conductor Operating Temperature : 70°C | BS 6346 |
| Ambient Temperature : 30°C |
Conductor |
2-core |
2-core cable single-phase a.c. |
2-core cable single-phase a.c. 3 |
Direct in ground |
Direct in ground |
||||||
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
||||
mm2 |
mV/A/m |
mV/A/m |
mV/A/m |
mV/A/m |
mV/A/m |
mV/A/m |
mV/A/m |
||||
1.5 |
29 |
|
29 |
|
|
25 |
|
29 |
25 |
29 |
25 |
2.5 |
18 |
|
18 |
|
|
15 |
|
18 |
15 |
18 |
15 |
4 |
11 |
|
11 |
|
|
9.5 |
|
11 |
9.5 |
11 |
9.5 |
6 |
7.3 |
|
7.3 |
|
|
6.4 |
|
7.4 |
6.4 |
7.4 |
6.4 |
10 |
4.4 |
|
4.4 |
|
|
3.8 |
|
4.4 |
3.8 |
4.4 |
3.8 |
16 |
2.8 |
|
2.8 |
|
|
2.4 |
|
2.8 |
2.4 |
2.8 |
2.4 |
|
|
r |
x |
z |
r |
x |
z |
|
|
|
|
25 |
1.75 |
1.75 |
0.17 |
1.75 |
1.5 |
0.145 |
1.5 |
1.7 |
1.5 |
1.7 |
1.5 |
35 |
1.25 |
1.25 |
0.165 |
1.25 |
1.1 |
0.145 |
1.1 |
1.3 |
1.1 |
1.3 |
1.1 |
50 |
0.93 |
0.93 |
0.165 |
0.94 |
0.8 |
0.14 |
0.81 |
0.94 |
0.82 |
0.94 |
0.82 |
70 |
0.63 |
0.63 |
0.16 |
0.65 |
0.55 |
0.14 |
0.57 |
0.66 |
0.57 |
0.66 |
0.57 |
95 |
0.46 |
0.47 |
0.155 |
0.5 |
0.41 |
0.135 |
0.43 |
0.49 |
0.42 |
0.49 |
0.42 |
120 |
0.36 |
0.38 |
0.155 |
0.41 |
0.33 |
0.135 |
0.35 |
0.4 |
0.35 |
0.40 |
0.35 |
150 |
0.29 |
0.30 |
0.155 |
0.34 |
0.26 |
0.13 |
0.29 |
0.34 |
0.29 |
0.34 |
0.29 |
185 |
0.23 |
0.25 |
0.15 |
0.29 |
0.21 |
0.13 |
0.25 |
0.29 |
0.25 |
0.29 |
0.25 |
240 |
0.18 |
0.19 |
0.15 |
0.24 |
0.165 |
0.13 |
0.21 |
0.24 |
0.21 |
0.24 |
0.21 |
300 |
0.145 |
0.155 |
0.145 |
0.21 |
0.135 |
0.13 |
0.185 |
0.21 |
0.18 |
0.21 |
0.18 |
400 |
0.105 |
0.115 |
0.145 |
0.185 |
0.1 |
0.125 |
0.16 |
0.19 |
0.17 |
0.19 |
0.17 |
![]()


(s) : Sector Shaped Stranded Conductors